| INFRATEK | Switzerland | DC27 - Battery Load Unit |
|
|
|
| Introduction | DC27 Load Test Models | Specifications | Application Examples | Datasheet |
Control Module
|
Master Load / Slave Load, LD260, LD60
Master Load / Slave Load, LD100
|
IntroductionThe Infratek DC27 Loads offer the user versatility, flexibility, lightweight, and sturdy design, combined with precise measurement technique to obtain complete battery information, or UPS- and generator characteristic. Three load types are available: LD260 and LD60 are DC- as well as AC-Loads for up to 600V, 1200A, 100kW; LD100 is a DC-Load for 1V / 100A up to 100V/8A. |
Versatile Battery Load UnitBattery Load Units measure capacity of back-up batteries by means of a discharge
test. Premature capacity decrease, weak blocks, or weak cells are detected. Periodic tests assure
crucial equipment to run in case of power failure. |
Versatile 50Hz / 60Hz LoadOne master load and one slave load can be connected to form a 50Hz, 60Hz single phase resistive load for 230V/113A - or 400V/65A operation. The load current is set in the SETUP menu of the control module. The load characteristic is constant current, constant power, or constant resistance. Three phase loads, star - or delta connected, can be configured using one master load and five slave loads. Maximum power for a basic 3-phase load is 78kW. By parallel connecting slave loads, power can be increased to a maximum of 390kW. |
Easy To UseThe DC27 load bank in its minimal configuration consists of the control module
and a master load. To start a discharge test you simply connect the control cables to the load,
energize the load, set in the SETUP menu of the control module the desired discharge current, number
of cells, and final cell voltage. Also, select the discharge function F1. Connect the master load to
the battery, connect the voltage measuring cable from the control module to the battery poles, and
press the START key. The monitor displays discharge current, voltage at the battery poles, charge,
energy, time, cell voltage, and in a reserved text field presents status, warnings, or errors. |
High PerformanceWith only three different load types the user can discharge batteries in the
whole voltage range up to 600V. Series connected loads can discharge high voltage batteries.
Very large currents are obtained by parallel connection. The control module commands all load types
and does the controlling based on the programmed criteria constant current,- power,- resistance. It
performs precision measure-ments of discharge current, (no current clamps are needed) battery voltage,
charge, energy, elapsed time, and cell- or block voltages. Battery data are accumulated and can be
saved in nonvolatile memory. During discharge you have the option to read cell - or block voltages
into the control module memory. Values of up to 100 cells can be entered. |
DC27 DC- and AC-Loads
| ||||||||||||||||||||
Options
| ||||||||||||||||||||
Accessories
|
| CONTROL MODULE - controls all loads, acquires and displays battery- or UPS dada | |||||||||||||||||
| Main Functions | Selectable by soft keys F1: Battery discharge; F2: Float Charge Optimizer; F3: Charge Optimizer; F4: Step load testing on large DC power supplies; F5: Load Testing on AC-supplies / UPS |
Up to 5 functions in a Control Module |
|||||||||||||||
| Current | Ranges 12A, 40A, 120A, 400A, 1200A (max. 1600A) Accuracy: ±(0.2% of reading + 0.3% of range); 23°C ± 3°C |
Auto-ranging 30% to 140% of range |
|||||||||||||||
| Voltage Cell Voltage |
Ranges 1V, 3V, 10V, 30V, 100V, 300V, 1000V, max. 600V Accuracy: ±(0.2% of reading + 0.3% of range); 23°C ± 3°C |
Auto-ranging 30% to 140% of range |
|||||||||||||||
| Charge | Ranges mAh, Ah, kAh, MAh; 5 digits Accuracy: ±0.5% of reading; 23°C ± 3°C |
Auto-ranging Charge / Discharge |
|||||||||||||||
| Energy | Ranges mWh, Wh, kWh, MWh; 5 digits Accuracy: Add accuracy %-figures of current and voltage |
Auto-ranging Charge / Discharge |
|||||||||||||||
| Time | Accuracy: ±0.1%; display in decimal notation | e.g. 3.5002h | |||||||||||||||
| Estimated Charge | Accuracy: ±5% typical | Lead Acid Batteries | |||||||||||||||
| Display | Blue liquid crystal graphic display with EL backlight, temperature compensated. Displays 6 values (5 digits and decimal point) incl. units. 40% of display is reserved for help and status information. Plots are drawn on full size display |
58 x 108mm; 128 x 240 pixels |
|||||||||||||||
| Load Control |
|
|
|||||||||||||||
| Options | - RS232 incl. Infratek Windows Battery Analysis Software - Cell voltage measurement - Clamp input 0-200A. Is used when battery during discharge remains connected to equipment it serves. |
Windows 95, 98, 98SE NT, ME, 2000, XP |
|||||||||||||||
| Dimensions Weight / Case Dielectric Strength Temperature |
75 x 160 x 245mm 1.2kg / light gray plastic case voltage input to case: current path to case: 0-30°C operating, -10-50°C storage |
2kV 2kV |
|||||||||||||||
| LD260 - Master Load, Slave Load; Application: Utility-UPS testing up to 600V; 1- and 3-phase AC-testing | |||||||||||||||||
| Max. Values | 260V, 13kW, 70A; max. 3 loads in series at 600V total | Max. 8 loads in parallel | |||||||||||||||
| Characteristic | 190-260V: max. current = 13kW/voltage; <190V: max. current in A = 0.375 x (voltage - 3V) |
Rise time = 50us | |||||||||||||||
| Discharge Examples 204 cells; 1.8V/cell 180 cells; 1.8V/cell 120 cells; 1.8V/cell 54 cells; 1.8V/cell |
600-540V: 3 series loads, const. current 0-66A 540-480V: 3 series loads, const. current 0-59A 440-367V: 2 series loads, const. current 0-59A 390-324V: 2 series loads, const. current 0-59A 258-216V: 2 parallel loads, const. current 0-100A 116-97V: 2 parallel loads, const. current 0-70A |
max. 13kW per load max. 11kW per load max. 13kW per load max. 11.5kW per load max. 13kW per load max. 4kW per load |
|||||||||||||||
| Protection | Control unit shuts off loads when maximum is exceeded | - | |||||||||||||||
| Mains Supply | 90-240V / 50Hz, 60Hz / 30VA; IEC socket with switch | - | |||||||||||||||
| Weight Dimensions | 8.5kg, Carrying Strip; H x W x D = 600 x 300 x 250mm | Light gray finish | |||||||||||||||
| Dielectric Strength | Load section to mains ground | 2kV | |||||||||||||||
| Temperature | 0-35°C operating | - | |||||||||||||||
| LD60 - Master Load, Slave Load; Application: Telecom-Traction-Utility, DC-supply testing | |||||||||||||||||
| Max. Values | 60V, 9kW, 150A; max. 4 loads in series | max. 8 loads in parallel | |||||||||||||||
| Characteristic | 40-60V: max. current = 150A; <40V: max. current in A = 4 x (voltage - 3V) |
Rise time = 50us | |||||||||||||||
| Discharge Examples 54 cells; 1.8V/cell 30 cells; 1.8V/cell 24 cells; 1.8V/cell 24 cells; 1.8V/cell 12 cells; 1.8V/cell |
116-97V: 2 series loads, const. current 0-150A 64-54V: 1 load, const. current 0-150A 52-43V: 1 load, const. current 0-150A 52-43V: 4 parallel loads, const. current 0-600A 26-21V: 4 parallel loads, const. current 0-288A |
max. 8.7kW per load max. 9.6kW max. 7.8kW max. 7.8kW per load max. 1.9kW per load |
|||||||||||||||
| Protection | Control unit shuts off loads when maximum is exceeded | - | |||||||||||||||
| Mains Supply | 90-240V / 50Hz, 60Hz / 30VA; IEC socket with switch | - | |||||||||||||||
| Weight Dimensions | 8.5kg, Carrying Strip; H x W x D = 600 x 300 x 250mm | Light gray finish | |||||||||||||||
| Dielectric Strength | Load section to mains ground | 2kV | |||||||||||||||
| Temperature | 0-35°C operating | - | |||||||||||||||
| LD100 - Master Load, Slave Load; Application: Single cell-, Telecom-, DC-supply testing | |||||||||||||||||
| Max. Values | 100V, 100A at 1V, 800W per load | Max. 8 loads in parallel | |||||||||||||||
| Characteristic | Max. current = 800W/voltage; max. 100A | Rise time = 20us | |||||||||||||||
| Discharge Examples 24 cells; 1.8V/cell 6 cells; 1.8V/cell |
52-43V: 1 load, const. current 0-19A 13.2-10.8V: 3 loads, const. current 0-227A |
limited by 800W/52V limited by 2.4kW/13.2V |
|||||||||||||||
| Protection | Shuts off when current, voltage or power exeeded | 100V, 100A, 800W | |||||||||||||||
| Mains Supply | 90-240V / 50Hz, 60Hz / 30VA; IEC socket with switch | - | |||||||||||||||
| Weight Dimensions | 6.5kg, Carrying Strip; H x W x D = 430 x 300 x 250mm | Light gray finish | |||||||||||||||
| Dielectric Strength | Load section to mains ground | 2kV | |||||||||||||||
| Temperature | 0-35°C operating | - | |||||||||||||||
| Analog Input Analog Output |
0-5V / 10kΩ; sesitivity = 1A/50mV 0-2.5V / 10kΩ; sesitivity = 25mV/A |
Max. 10kHz square wave Current wave form |
|||||||||||||||
![]() |
A. Two DC27 Loads of the same type (LD100, LD60, LD260) are connected in parallel. Twice the current of a single Load can be drawn from the battery. The currents drawn by the loads are joined in the current junction box. |
![]() |
B. For high voltages, loads of the same type can be series connected (LD60, LD260). Example shows two loads in series; Load at top is series connected to load at bottom. Maximum battery voltage allowed is twice the maximum voltage of one load. The two series combinations are connected in parallel. The currents of the two series combinations are summed in the current junction box. |
![]() |
C. Two LD260 (1Master, 1 Slave) form one AC-Load UPS testing. Maximum values are 260V/26kW/50, 60Hz. |