Yields Correct Power For Any Wave Form
|
The ITL101 Broad Band DC-50kHz Power Transmitters are available as
single-phase, 2-phase (ARON), 3-phase, and multi-phase versions
(e.g. channel 1/2 in ARON, 0-20mA output; channel 3 for DC-power, 0-5V output).
In addition to the standard current- and voltage ranges special ranges for
current 10mA-20A, and voltage, 10V-600V, can be supplied. 3000Vac channel to
channel - and channel to output isolation results in maximum freedom for input
connections. The ITL101 withstands fast common mode transients and can be used
in frequency inverters and other electronically switched loads. Available
options are: DC-100kHz, non-standard voltage range, non-standard current range,
40ms response output for process control, energy output (3600 pulses per hour
for full scale), bipolar output to measure recuperated power, and single- and
three phase 0-100A current sensors.
|
ITL-101 Selection Guide
| Selections: |
ITL101-1: Single phase transmitter, specify voltage and current
ITL101-2: 2-phase transmitter (ARON), specify voltage and current
ITL101-3: 3-phase transmitter, specify voltage and current
ITL101-4: 2-phase transmitter (ARON), output 0-20mA; 1-phase transmitter
output 1, 0-5V, specify voltages and currents. |
|
Options
| Option |
Description |
| 01 |
Frequency range DC-100kHz |
| 02 |
Non-standard voltage range, specify |
| 03 |
Non-standard current range, specify |
| 04 |
40ms response time for process control |
| 05 |
Energy output, 3600 TTL-pulses per hour at full scale |
| 06 |
Bipolar output 0-±20mA, 0-±5V |
| 07 |
Single- and three phase current sensor 0-100Arms / 150A dc.
Wire size 7x12mm, case 70x100x142mm. |
|
| ITL-101 Transmitter |
Current Ranges In |
ITL101-1/2/3/4: 1A, 2A, 5A, 10A, 20A; working range: 0-150 %; DC-50kHz |
| Voltage Ranges Un |
ITL101-1/3: 120V, 250V; ITL101-2/4: 200V, 400V; working range: 0-150 %; DC-50kHz |
| Power Ranges |
ITL101-1: voltage x current;
ITL-101-2: 2 x voltage x current;
ITL101-3: 3 x voltage x current;
corresponds to 20mA or 5V. |
| Power Accuracy |
40-400Hz: 0.1 % reading +0.2 % range (0.2 % typical) 0≤PF≤1;
DC, 400-1000Hz: 0.3 % reading +0.2 % range, 0.7≤PF≤1;
1kHz-10kHz: 1 % typical |
| Output |
0-20mA, 0-5V; Bipolar output optional |
| Overload continuous |
Voltage: 1.5 x Un; current: In/10A, 3 x In; In = 20A, 1.5 x In. |
| Overload 1 second |
Voltage: 3 x Un; current: In/10A, 5 x In; In = 20A, 2 x In. |
| Input-output isolation |
3kV / 50Hz / 1 minute |
| Temp. coefficient |
-10°C to + 50°C; 0.002 % / deg. C |
| Supply |
230V / 50Hz / 3VA; 115V/60Hz/3VA |
| Case |
Light gray. Polycarbo / ABS case, wall mounting (M4 x15, 85 x 50mm)
Support rail mounting (DIN EN 50022-35) |
| Size/Weight |
H x W x D = 70 x 100 x 115mm; 400gr. |