INFRATEK Switzerland ITL-300 Transmitter





ITL-300 Power Transmitter





ITL-300 Models Specifications Datasheet

Introduction

The 3-phase Power Transmitter ITL-300 measures power in 3-phase systems. Due to its wide frequency range DC-10kHz, it can also be used to measure power in thyristor controlled circuits and frequency inverter systems.
The 0-20mA output signal is galvanically isolated from the transmitter input circuitry. In the 50/60Hz three phase system current is measured via current transformers. In thyristor controlled circuits with high current harmonics and in variable frequency inverter systems current must be measured via Hall sensors.

ITL-300 current ranges 50mA / 100mA / 200mA are provided for current outputs from Hall sensor modules. A 3-phase current sensor module for current ranges 25A / 50A / 100A is available.




Top

ITL-300 Versions

Product Description
ITL-300-3 Three Phase Power Transmitter, 0.3%, DC-10kHz
ITL-300-1 Single Phase Power Transmitter, 0.3%, DC-10kHz
ITL-300-3 Three Phase Power Transmitter, Low Cost Version, 1.5%
ITL-300-1 Three Phase Power Transmitter, Low Cost Version, 1.5%

Options

Option Description
01 Three phase current sensor module,
0.5%, DC-10kHz, requires +12V/300mA supply




Top

ITL-300 Specification (20°)

ITL-300 Transmitter Current Ranges 1A, 5A for current transformers, overload 50A, 0.4sec.
50mA, 100mA, 200mA for Hallsensor current transformers
Voltage Ranges Nominal 250V linear up to 400V. Max. input 4x nominal voltage.
Special ranges available, min. 10V
Power Range (per phase) P = IxU; 250W and 1250W for current transformer;
12.5W, 25W, 50W for Hallsensor current transformers
Frequency range Voltage: DC-50kHz
Current: DC-20kHz
Accuracy Output curr. >1mA. 20-200Hz, ±0.3% (typ.0.2%) of output
DC-1kHz, ±0.8% of output
1-10kHz, ±2% of output
At PF smaller 0.5 multiply accuracy percentage by 2.
Output 0-20mA for nominal power range,
max. linear output 0-30mA (Positive output currents only).
Overload Voltage: 4 times nominal range;
Current: 10 times nominal range, 0.4sec.
Linearity ±0.1%, 2-25mA
Input resistance 500kΩ for nominal voltage range
Measuring resistance 0.1Ω for 1A- and 5A-range
Temp. coefficient 0.004mA/°C
Response time 1 sec. for 0-95%. 40ms Option 1
Crest factor Max. 3 voltage and current
Input/Output isolation 2kV, 50Hz, 1 minute
Output load Rb -5uA/100Ω; 0-250Ω max. at 20mA
Common mode rejection 100dB, 50Hz
Ambient temperature -10° - +50°C
Supply 230V (+20%/-10%) / 50mA (110V on request)
Case Gray plastic case for wall mounting, or DIN46277
support rail mounting
Size H x W x D, 70 x 100 x 112mm
Weight 400gr.